On January 4, 2024, the Unit 1 was operating at 100% power. At 09:00 (local time) the steam tunnel cooling unit “1-RRA-FC-009A” was started due to equipment rotation resulting in the loss of energy in the Motor Control Center (MCC) “1-R31-MCC-1BA-AA” with the failure of the electrical protection of the cubicle 5D of the MCC “1-R31-MCC-1BA-A”.At 09:05, the Auxiliary Reactor Operator reported the presence of smoke in the MCC “1-R31-MCC-1BA-A” preventing the manual opening of the cubicle 5D.At 09:10, the Auxiliary Turbine Operator reported that the switch 7A that energize the MCC “1-R31-MCC-1BA-A” could not be manually open.At 09:17, the Auxiliary Reactor Operator reported the presence of fire in the MCC “1-R31-MCC-1BA-A” located in the elevation 18.70 of the Reactor Building. The bus 14BA was de-energized by manually opening the switches 14BAM and 14BA resulting in entry to the procedure 1-OA-0556 "Loss of 4160/480VAC non-critical". The fire brigade was activated according to the procedure PAS-32 "Fire Protection Program".At 09:32, an Unusual Event was declared due to fire in the protected area not extinguished in 15 minutes (NUP-4.1). At 09:45, the Chief of the fire brigade reported that the event had been controlled and that maneuvers to recover the area would begin.At 13:30, the Unusual Event was declared finalized.